Heating, ventilation and alarms for a basement suite
One furnace and two households needs a plan.
A new house cannot use one forced air system for two units. An existing house may keep a shared system under conditions, mainly interconnected alarms and a smoke detector in the ductwork that shuts the system down. Each unit also needs its own temperature control. We plan this early in basement apartment construction.
Can the existing furnace serve the suite?
In a building with four or fewer units, the existing system may be altered to serve more than one, provided there are smoke alarms in each unit and a duct smoke detector that cuts fuel and power to the heating system. The other route is a separate system, such as a heat pump or radiant heat.
What about fresh air?
Each unit is to have its own ventilation. A heat recovery ventilator is not required where an existing house is converted from one unit to more, though rooms still need natural or mechanical ventilation. Bathroom and kitchen exhaust should go outdoors.
Where do smoke alarms go?
- On every storey.
- In every sleeping room.
- Between sleeping rooms and the rest of the storey.
- In shared exit routes and common spaces.
They are to be interconnected where more than one is needed, and in new work wired in with battery backup.
When are carbon monoxide alarms needed?
Where there is a fuel-burning appliance or an attached garage. They go next to sleeping areas, and in some cases inside the bedroom itself, for example when it shares a ceiling or wall with a space holding a fuel-burning appliance. Gas work should be done by a TSSA registered contractor.
Common questions
Does the tenant need a thermostat?
Yes. The Town's guide asks for separate temperature control in each unit, with at least one programmable device.
Is an electrical permit needed for alarms?
Electrical work is filed with the Electrical Safety Authority, separately from the building permit.
How warm must the suite be kept?
The Town's property standards checklist says heat must keep rooms at 21 degrees Celsius or more.
Related pages
Separate Entrance
The door is where privacy, safety and the foundation all meet.
Egress Windows
A bedroom window is only an exit if a person can get through it.
Fire Separation
The ceiling over the suite is a safety system, not a finish.
Check your basement before you build
Have these ready:
- Age and type of house
- Ceiling height, including under ducts
- Any door from the basement to outside
- How many cars the driveway holds